Connection of FOCUS & Muting Components with FMC1 and FMI1
|
|
Connection of light curtain with connection block FMC 1, text/reset button 1 and switch for supply voltage laced in or by the control cabinet.
 |
Connection of light curtain with connection block FMC1. The FMI reset unit must be placed out of reach from the risk area.
 |
Connection of FOCUS & Muting Directly to Control Cabinet
|
 |
The test/reset button shall be placed so the operator can see the protected area during reset, testing and bypassing, It should not be possible to reach the button from within the risk area.
The LMS lamp for indication of muting and bypassing shall be placed so that it can be seen from all directions from where it is possible to access the dangerous area.
If photocells are used as muting sensors, the sensor receivers should be assembled on the light curtain's transmitter side to minimize the interference risk.
The system is protected against dangerous functions caused by damage on the transmitter cable and/or the receiver cable. However, we recommend that the cables be protected so that physical damage to them can be minimized.
|
|
Connector View from Cable Side
|
 |
 |