Ordering Data
120 VAC (3NO/1NC)............... JSNA-MLC-31-120
24 VDC (3NO/1NC)................... JSNA-MLC-31-24
Ambient Air Temperature
Operation......................................... -40ºC to +60ºC
Storage............................................. -55ºC to +70ºC
Maximum Altitude........................................ 3000 m
Operation Position
Normal.......................................... On vertical plane
Allowable......................................................... +/- 30º
Mounting.... screw or 35mm DIN rail (EN 50022)
Pole Characteristics
Poles......................................................................... 4
Rated Thermal Current lth ( £40ºC)................ 10A
Rated Insulation Voltage Ui........................... 690V
Frequency Limit.................................... 25 - 400 Hz
Designation of Auxiliary Contacts
according to IEC/EN 60947-5-1 UL/CSA
AC.................................................................. A600
DC................................................................. Q600
Terminals A............................................... 7.5 mm
B.................................................. 4 mm
Screw.............................................. M3
Maximum Tightening Torque
for Contact Terminals................................... 1 Nm
Maximum Tightening Torque
for Coil Terminals.......................................... 1 Nm
Maximum Wire Section Connectable
with 1 or 2 Conductors
AWG.................................................................. 12
Flexible w/o Lug
(min-max)............................ 0.75mm2/2.5mm2
Flexible c/w Lug........... 2-1mm2 or 1-2.5mm2
Terminal Protection
according to EN 60529.................................. IP20 (min 0.75mm2/18AWG section)
AC Control
Rated Control Voltage at
50, 60, 50-60Hz............................................... 120V
Operating Voltage Limits
Pick-Up......................................... 75 - 115% Us
Drop-Out......................................... 30 - 55% Us
Average Coil Consumption
50 Hz in rush/holding............................ 30/4 VA
60 Hz in rush/holding............................ 25/3 VA
Dissipation at 50 HZ................................... 0.95 W
DC Control
Rated Control Voltage...................................... 24V
Operating Voltage Limits
Pick-Up......................................... 70 - 115% Us
Drop-Out......................................... 10 - 20% Us
Average Consumption.................................. 3.2 W
Mechanical Life
AC and DC (millions)............................. 20 cycles
Maximum Operating Cycle............ 3600 cycles/h
Operating Times
AC with Control
Closing NO....................................... 12 - 21 ms
Opening NO........................................ 9 - 18 ms
Closing NC....................................... 17 - 26 ms
Opening NC........................................ 7 - 17 ms
DC with Control
Closing NO....................................... 18 - 25 ms
Opening NO.......................................... 2 - 3 ms
Closing NC............................................ 3 - 5 ms
Opening NC...................................... 11 - 17 ms
Pole Characteristics Minimum Switching Rating...................... 1mA/5V