Manufacturer.............................. JOKAB SAFETY
Ordering Data............... RT6 and supply voltage
Color............................................. black and beige
Weight..... 335 g (24 VDC), 485 g (24-230 VAC)
Supply
Voltage (A1-A2)..................... 24 VDC +15/-20%,
24/48/115/230 VAC, +/-15%, 50-60 Hz
Power Consumption
DC supply, nominal voltage..................... <2.4 W
AC supply, nominal voltage....................... 5.3 VA
Connections S13............ Short-circuit protected
voltage output,
70 mA +/- 10% current limitation.
Is used for the inputs S14, S34 and S44
Connections S53............ Short-circuit protected
voltage output,
internal automatic fuse, max 270 mA.
Is used for the reset and
autoreset inputs X1 and X4
Connections S23. 0V connection for input S24
Safety Inputs
S14.............................................. +24 VDC, 20 mA
S24................................................... 0 VDC, 20 mA
S34.............................................. +24 VDC, 20 mA
S44.............................................. +24 VDC, 30 mA
Reset input X1
Supply for reset input............................. +24 VDC
Reset current............... 300 mA current pulse at
contact closure, then 30mA
Minimum contact
closure time for reset............................ <100 ms
Maximum external connection cable
resistance at nominal voltage for
S14, S24, S34......................................... 300 Ohm
S44, X1..................................................... 150 Ohm
Response Time
At Power on DC/AC.....................<90ms/<220ms
When activating (input-output).................<20 ms
When deactivating (input-output)............<20 ms
At Power Loss.......................................... <150 ms
Relay Outputs
NO........................................................................... 3
NC........................................................................... 1
Maximum switching
capacity res. load AC......... 6A/250 VAC/1500 VA
Maximum switching
capacity res. load DC............. 6A/24 VDC/150 W
Minimum load....................................... 10mA/24 V
(if load on contact has not exceeded 100 mA)
Contact material.......................... AgNi10+0.2µAu
Mechanical life............................ >107 operations
|
|
Transistor Outputs.................. Short-circuit proof
External supply to Y13................... +5 to +30 VDC
Y14..................................... Indicates that the input
conditions have been fulfilled
Y24................................... Indicates that the output
relays are activated
Maximum load of Y14, Y24........... .15 mA /output
Maximum voltage drop at maximum load... 2.4 V
LED Indication
On ..............Supply voltage OK, the LED is on
Flashing light in case of
under-voltage or overload
In 1 In 2 ................Indicates that the input
conditions are fulfilled
1 2 ...........Indicates that the output
relays are activated
Mounting Rail................................ 35 mm DIN rail
Operating Temperature
Range .......................................... -10° C to + 55° C
Connection Blocks (detachable)
Maximum screw torque................................. 1 Nm
Maximum connection area
Solid
conductors........... 1x4mm2/2x1.5mm2/12AWG
Conductor with
socket contact.................... 1x2.5mm2/2x1mm2
Air and creep distance........ 4kV/2 IEC 60664-1
Protection Class
Enclosure..................................... IP 40 IEC 60529
Connection blocks...................... IP 20 IEC 60529
|
|