Color................................................. black and beige
Weight................................................................ 210 g
Supply Voltage (A1-A2)................ 24 VDC +/- 20%
Power Consumption
DC supply, nominal voltage........................... 2.5 W
Connections S13............... short-circuit protected
voltage output
70 mA +/- 10% current limitation.
Is used for the inputs S14, S34, S44
Input currents (at nominal supply voltage) S14 (+) input................................................... 30 mA
S24 (0V) input................................................. 20 mA
S34 (+) input................................................... 20 mA
S44 (+) input................................................... 25 mA
Reset input X1 Supply for reset input................................ +24 VDC
Reset current................... 300 mA current pulse at
closure, then 30mA
Minimum contact
closure time for reset.................................. <80 ms
Minimum contact closure time (at low limit voltage -20%)......................... 100 ms
Maximum external connection cable
resistance at nominal voltage for S14, S24, S34............................................. 300 Ohm
S44, X1......................................................... 150 Ohm
Response Time
At Power on................................................. <100 ms
When activating (input-output)................... <20 ms
When deactivating (input-output).............. <20 ms
At Power Loss.............................................. <80 ms
Relay Outputs
NO................................................................................ 2
Maximum switching
capacity res. load....... 6A/250 VAC/1500 VA/150W
Maximun switching
capacity res. load DC................ 6A/24 VDC/150 W
Minimum load.......................................... 10mA/10 V (if load on contact has not exceeded 100 mA)
Contact material............................................. AgCdO
Mechanical life................................ >107 operations
Relay Information Output
(Changeover contacts) Y14 - (0V)................ Indicates that RT9 is not reset
+ (24V)....................... Indicates that RT9 is reset
Maximum load of Y14................................... 250 mA
Short-circuit protection
for information output..... Internal automatic fuse
LED Indication
On..................Supply voltage OK , the LED is on
Flashing light in case of
under-voltage or overload In 1 In 2 .......................Indicates that the input
conditions are fulfilled 1 2 ..............Indicates that the output
relays are activated
Mounting Rail................................... 35 mm DIN rail
Operating Temperature
Range............................................. -10° C to + 55° C
Connection Blocks (detachable) Maximum screw torque.................................... 1 Nm
Maximum connection area
Solid
conductors............... 1x4mm2/2x1.5mm2/12AWG
Conductor with
socket contact........................ 1x2.5mm2/2x1mm2
Air and creep distance.............. 4kV/2 IEC 60664-1
Protection Class
Enclosure........................................ IP 40 IEC 60529
Connection blocks......................... IP 20 IEC 60529